The Ranco ETC-212000 is identical to the Ranco ETC-112000 except that this unit is 2 stage, and has 2 relays to control both heating and cooling at the same time. (The output relay NC and NO ratings are also different)
Specifications: Temperature Setpoint Range: -30° to 220°F Differential range: 1° to 30°F Input Voltage: 24VAC Pilot duty: 125VA at 120/208/240VAC Sensor: Thermistor, 2" long x 1/4"dia with 8' cable (included) Control Ambient Temperatures Operating: -20° to 140° Storage: -40° to 176° Ambient humidity: 0 to 95% RH, non-condensing Enclosure: NEMA 1 Dimensions: 6.52" high x 2.7" wide x 2.48" deep Agency Approvals: UL listed, file E94419, Guide XAPX, CSA certified, file LR68340, class 4813 02 Relay Output Ratings - NO (NC) 120V 208/240V Full load amps 9.8 (5.8) A 4.0 (2.9 A) Locked rotor amps 58.8 (34.8) A 29.4(17.4) A Resistive amps 9.6 (5.8) A 4.9 (2.9) A Horsepower 1/2 (1/4) HP 1/2 (1/4) HP Unsure which Ranco ETC Controller you need? Check out our ETC Selector.
Relay Output Ratings - NO (NC)
120V
208/240V
Full load amps
9.8 (5.8) A
4.0 (2.9 A)
Locked rotor amps
58.8 (34.8) A
29.4(17.4) A
Resistive amps
9.6 (5.8) A
4.9 (2.9) A
Horsepower
1/2 (1/4) HP